Description
KDGC Series Diesel Generator Sets
Powered by Cummins Engines
KDGC35S 50HZ
Ratings
Standby Power
KVA
44
KW
35
Prime Power
KVA
40
KW
32
Voltage type
50Hz,380/220V, 3 phases and 4 wires
Ratings at 0.8 power factor
1) Standby Power – Power available at a variable load when a main power network fails, running up to a maximum of 500 hours per year. Over load is not allowed.
2) Prime Power – Power available at variable load in lieu of main power network. An overload of 10% is allowed for one hour in every twelve hours of operation.
Performance Data
Engine Brand & Model
Cummins 4BT3.9-G2
Alternator Brand & Model
Leroy Somer LSA42.3 S5
Control System
Deepsea DSE6120
Standard Noise Level@7m (Soundproof Sets)
75 dBA
Circuit Breaker Type
3 Poles MCCB
Frequency & Phase
50hz 3Phases + 4Wires
Engine Speed (RPM)
1500
Fuel Consumption (L/hr)
100% Load
9.3
75% Load
7.6
50% Load
5.1
25% Load
2.6
Dimensions and Weights
Content
Open type
Soundproof Sets
Dimensions: (mm)
L
1700
2370
W
760
1100
H
1400
1650
Weights (kg)
850
1462
Engine Brand & Model: Cummins 4BT3.9-G2
Standard Cummins Engine Data
No. of Cylinders
4 vertical in-line
Gross Engine Power (kW)
Prime
36
Cycle
4 Stroke
Standby
40
Bore * Stroke (mm)
102 * 120
Compression Ratio
16.5:1
Induction
Turbocharger
Displacement (L)
3.9
Cooling Method
Water cooled
Governing Type
Electrical
Starting method
24V DC motor
Coolant capacity engine only (L)
7.2
Lubricant Oil
15W40-CF4 or above grade
Lube System Capacity (L)
11
Alternator Brand & Model: LSA42.3 S5, 50Hz.
Standard Leroy Somer Alternator Data
Continuous power
40KVA / 32kW
Efficiency (%)
89.6
Power factor
0.8
Temperature rise
125K
Excitation system
Shunt
Insulation class
H
A.V.R.
R220
Enclosure protection
IP23
Voltage regulation
± 0.5 %
Winding leads
6
Bearing number
1 bearing
Ambient temperature (°C)
40
Controller Brand & Model: Deepsea DSE6120
The DSE6120 is an Auto Start & Auto Mains (Utility) Failure Control Module suitable for a wide variety of single, diesel or gas, gen-set applications. It monitors speed, frequency, voltage, current, oil pressure, coolant temperature and fuel level, and the modules will display warnings, shutdown and engine status information on the back-lit LCD screen and illuminated LED.
The controller offers electronic (CAN) and non-electronic (magnetic pick-up/alternator sensing) engine versions and offer a number of flexible inputs, outputs and engine protections so the system can be easily adapted to suit a wide range of application demands.
The controller can also be easily configured using the DSE Configuration Suite PC software. Selected front panel editing is also available.
Reviews